Description:
1) ANSI, IEC Standard2) Pin Type
3) 55-1, 55-2, 55-3, 55-4, 55-5 series
4) Factory
5) Test Report
IEC HV Porcelain Disc Insulators ANSI55-4
1) DRAWINGSHOW:
2)MAIN DIMENSIONS AND STANDARD PARTICULARS:
Class ANSI | 55-4 | ||||
Fig. NO | 4 | ||||
NO. Used Before | P-10-M | ||||
Main Dimensions mm | H | 111.2 | |||
h | 44.5 | ||||
D | 129.6 | ||||
d | 25.4 | ||||
R1 | 25.4 | ||||
R2 | 14.3 | ||||
Nominal Voltage/KV | 10 | ||||
Creepage Distance/mm | 229 | ||||
Minimum FlashoverVoltage | Power-Frequency | Dry/KV | 70 | ||
Wet/KV | 40 | ||||
50% Impulse | Positive/KV | 110 | |||
Negative/KV | 140 | ||||
Radio-Influence-VoltageDate | Test Voltage toGround/KV | 10 | |||
Maximum RIV at1000kHz/KV | 5500 | ||||
Low Frequency Puncture VoltageAverage/KV | 95 | ||||
Dry ArcingDistance(mm) | 127 | ||||
Cantilever FailingLoad(id) | 3000 | ||||
Weight/kg | 2.25 | ||||
3)PRODUCT SHOW:
4)INSULATOR PROCESS DEscriptION:
5)OTHER RELATED PRODUCT:
We sincerelyhope our products can service more and more clients from all overthe world, so, if you are interested in our products, please don''thesitate to contact us.
Lookingforward to your reply! We will arrange everything foryou.
Pls contact Mercy for moreinfo.