Description:
1. Excellent temperature characteristic and good working stability2. A variety of models can be choosedFunction& Feature of GFUVE single phase currenttransducer
Transformsthe measured AC current/voltage to the DC current/voltage outputaccording to the linear scale
Excellenttemperature characteristic and good working stability
Configurationcompactness and briefness
ModelDescription
FUD-Type-Input-PowerSupply-Output | |
Type | I: SinglePhase AC Current Transducer U: SinglePhase AC Voltage Transducer Ir: SinglePhase AC Real RMS Current Transducer Ur: SinglePhase AC Real RMS Voltage Transducer |
ACInput | A1: 0~1A,A2: 0~5A, A3: 0~10A. V0: 0~70V,V1: 0~120V, V2: 0~250V, V3: 0~300V,V4: 0~450V, V5: 0~500V. |
PowerSupply | P1:AC110V±10%, P2: AC220V±15%, P3:AC110V~330V. |
DCOutput | O1: 0~5V,O2: 1~5V, O3: 0~20mA, O4: 4~20mA,O5: RS485. |
Example 1:FUD-I-A2-P2-O4 | |
FUD SeriesSingle Phase AC Current Transducer | Input:AC0~5A |
PowerSupply: AC220V±15% | |
Output:DC4~20mA | |
Example 2:FUD-Ur-V3-P2-O4 | |
Details:FUD Series Single Phase AC Real RMS Voltage Transducer | Input: AC0~300V |
PowerSupply: AC220V±15% | |
Output:DC4~20mA | |
Pleasecheck the Type, Input range, Output range and Power supply at yourorder. | |
TechnicalIndex
Standard | GB/T13850-1998, IEC688:1992 |
Accuracy | 0.2%,0.5% |
Consumption | ≤3VA |
Accuracydrift | AnnualVariation < 0.2% |
InsulationVoltage | AC2kV/min.1mA (Between Input ~ Output / Power) |
InsulationResistance | ≥20MΩ(DC500V) |
Surgevoltage | 5KV (PeakValue), 1.2/50μs |
ResponseTime | ≤350ms |
InputRange | AC 0~10A ,AC 0~500V(Optional), 50/60Hz |
AbsorbedPower | <0.5VA/450V,<0.2VA/100V, <0.1VA/5A |
Overload | Current: 2times continuous, 30 times /1s .Voltage: 2 timescontinuous |
LoadResistance | Currentoutput: RL≤550Ω Voltageoutput: RL≥2kΩ |
Workingenvironment | Temperature:-10~50°C RH: 20~90%,Without condensation |
Storageconditions | Temperature:-40~70°C RH: 20~95%,Without condensation |
Installation | 35mm DINSliding-way or M4 screws |
Dimension | 55mm×75mm×120mm |