2, stable, reliable, a long life time
3, good for heat dissipation
4, 110kv voltage transformer
JDC6(F)-110 Outdoor oil-immersed 110KV voltagetransformer
Feature
1, It is cascade structure, which the primary winding hasfour grade windings surrounded on each limbs of one single phasetwo-limb core. The insulation consists of high voltage cable paper,phone paper and cardboard etc, which will be immersed withtransformer oil after desiccating under vacuum. It has advantage ofstable and reliable performance of insulation, rich successfulexperience, a long life time and convenient maintenance
2, Perfect fluidity performance of transformer oilis good for heat dissipation, italso has self recover ability for the failure of partial dischargecaused by air bubble and dust.
It has two or three secondarywindings, which has individual measuring and meteringwinding.
3, Hermetically sealed stainlesssteel metallic bellows is installed on the top, which protects thetransformer oil from moisture and extend the life time, also thereis a oil level gauge on the bellows for observing the changing ofoil volume
4, There is a multifunction oildrain valve on the base, which makes it more convenient forsampling and draining
5, The secondary terminal boardis made of epoxy casting, the seal performance is morereliable.
Technicaldata
Rated primary voltage | 132(110, 66)/√3Kv | ||||||
Highest voltage for equipment | 145(126, 72.5)√3Kv | ||||||
Rated frequency | 50 or 60 Hz | ||||||
Rated voltage ratio | 132(110,66) / 0.1 /0.1kv √3 √3 | 132(110,66) / 0.1 /0.1/0.1kv √3 √3√3 | |||||
Accuracy and rated output
| Secondary terminal marking | 1a-1n | 2a-2n | da-dn | |||
Accuracy | 0.2 | 0.5 | 0.5 | 3p | 3p | ||
30010 |
| 100 | 150 | 150 | 300 | 300 | |
Terminal limit output | 2000VA | ||||||
Accuracy voltage factor | 1.2 times continuous ;1.5times 30s | ||||||
Partial discharge under 1.2Um/√3Kv | ≤5Pc | ||||||
Dielectric dissipation factor tg under 10KV | product≤0.02; frame≤0.05 | ||||||
Power frequency withstand voltage on primary windings | 230(275) kv 200(230) kv 140kv r ms | ||||||
Rated lightning impulse withstand voltage | 550(650) kv 450(550)kv 325kv peak | ||||||
Power frequency withstand voltage on primary winding "N"terminal to earth | 5kv r ms | ||||||
Power frequency withstand voltage between secondary windings andto earth | 3kv r ms | ||||||
Mechanical strength(three direction) | 2000N | ||||||