MOQ:1
Specifications
stabilize busbar voltage2)Improve power factor
3)Eliminate harmonic current
4)Decrease grid loss
5)optimize reactive power
| Parameter | value |
| Ratedvoltage | AC220-1140V |
| operationvoltage | 0.8-1.1UN |
| Ratedfrequency | 50Hz/60Hz(option) |
| Capacitorwiring mode | Delta /Star(option) |
| switchingmode | cycle/sequence/codedcombination |
| responsetime | less than20ms |
| allowablemaximun over current | 1.3 times ofrated current |
| controlsteps | 1-12 /1-16(option) |
| multipleunits operation mode | parallel |
| powerloss | lessthan 0.5% |
| communicationmodes | modbus/RS485 /232/CAN/GPRS etc(option) |
| IP | IP40(customized) |
| coolingmode | aircooling |
| leading inmode | bottom /top/busbar (option) |
| altitude | lessthan 2000 M |
| ambienttemperature | 42°C/-5°C |
| ambienthumidity | lessthan 90% |
| operationenvironment | nocondensation,no corrupt gas,no conductive dust,no explosive andinflammable |
| installationrequirment | novibration,inclination ≤5 |
| switchingcharacteristic | Currentzero-crossing switching |
| harmonicdisplay | measureand display 2nd-25th |
| phasesequence protection | Faultphase, phase loss |
| thyristorprotection | over-temperatureprotection and self-recovery |
| LCDdisplay | realtime current and voltage |
| Emergencyprotection | emergencystop switch |
| compensationmode | three-phasecompensation,phase splitting compensation |
| protectionmode | overcurrent,over voltage,short-circuit,quick break |
Principles:
Lowvoltage reactive power compensation device (TSC/TSF) is thecompensating device based on switching operation of capacitor banksby thyristor. TSC mainly consists of control system,thyristor, capacitors and reactors.,Capacitor banks aredivided into multiple units to realize step control. TSC is able toimplement step regulating in reactive power, accuracy of regulatingdepends on numbers of multiple unit.Low voltage reactive powercompensation device (TSC/TSF) apply delta wiring. Tooptimize effect of reactive power compensating and harmonicfiltering, TSC capacity and branch configuration must be designed,according to reactive power variation and harmonic components fromnonlinear load.
Low voltage reactivepower compensation device introduction:
based onDSP(digital signal processing) control technology and Instantaneouspower control theory, Weisite low voltage reactive powercompensation device (TSC/TSF) with high-speed switching capabilityare designed to support the supply voltage of distribution systemsand to correct the power factor and eliminate the harmonic currentof connected loads. Thyristor zero-crossing switching switches areresistant to mechanical wear, operate without noise, and arecapable of practically transient-free switching, so it is moresafety than contactor switched capacitor banks.
Thyristorswitches:
Modularizeddesign: Integrated by zero-crossing triggering thyristormodule,
RC absorbedcircuit, fuse, radiator, fan, thermo switch.
zero-crossingtriggering thyristor module.
Transientfree and no noise during switching
Inputsignals are coupled with control signals by opticalisolation
Systemmeasures thyristor temperature in real-time
Phase loss/fault phase protection
Maintenancefree and long service life
Fast responsetime
.
Reactor ,Capacitor
Controller :Zero-crossingtriggering thyristor module