Brand:GUOLONG
MOQ:1000
Quantity:2
BV-D series RCCB Residual current circuitbreaker(without over-current protection) is suitable for the lineof AC 50/60Hz, voltage 240V(2pole)/415V(4pole), rated current up to63A. When there is human electricity shock or if the leakagecurrent of the line exceeds the prescribed value, it will cut offthe power rapidly to protect human safety and prevent the accidentdue to the current leakage. It can be used as infrequent changeoverof the line in normal situation.It is applicable to industrialsite, commercial site, tall building and civil house.
It complies with standard of IEC/EN61008.1 and GB16916.1
frame class | 63A |
Rated working voltage | 240/415V |
Rated frequency | 50/60Hz |
Rated working current | 16202532405063A |
Rated residual operating current | 0.03,0.1,0.3,0.5A |
Rated residual un-operating current | 0.015,0.05,0.15,0.25A |
Sensibility | A(DC)TypeAC Type |
Maximum operating time | In t≤0.1s , 5In t≤0.04 |
Rated making and breaking capacity | In≤50A 500A,In=63A 630A |
Limiting value of un-operating current | 6In |
Rated limiting short-circuit current | 6000A |
Pole number | 24P |
Mechanical life | 10000 |
Electric life | 4000 |
BV-D Residual Current CircuitBreaker RCCB