LK303 SF6 On Line Leakmeter System
2016-11-06 23:46  Views:260
Price:Negotiable
Brand:LINKEL
MOQ:1
Send Inquiry

LK303 On Line Leakmetersystem is based on the current power system to furtherimprove production safety requirements, for the staff to providethe physical protection of health and safety which in the roominstalled SF6 distribution equipment, and the design, developmentof intelligent online detection system.

System is mainly detected inambient air, the SF6 gas’ content and oxygen content, when the SF6gas content exceed standard  or the lack of oxygen in theenvironment,the system can real-time alarm, and automatically opento the ventilation fan and have the temperature and humiditytesting, the work of the state of voice prompts, Far EasTone alarm,historical data query and many other rich features.

System uses the latest DNIRinfrared sensor technology to real-time measurement of theconcentration of SF6. Can be achieved not only the purpose ofprotection of personal safety, but also to ensure the normaloperation of equipment; high stability of oxygen sensors foron-site staff to provide more reliable protection layer.

The system can be widely used ina variety of voltage levels of SF6 switch rooms, switchgear rooms(GIS Room), SF6 main transformer room.

 

Systeminstallation:

 

??? the whole system can beinstalled in the power state of equipment.

??? we responsible for on-siteinvestigation, construction, installation, commissioning work, theuser sent to custody at the scene.

??? users associations, we meet,conduct on-site inspection, record inspection results on behalf ofthe signing by the user.

??? construction after thecompletion of our responsibility to provide systems engineeringplans within one week.

 

Networksystem:

In order to fully and accuratelymonitor the situation at the scene, the project-site monitoring inaccordance with the scope, equipment, such as intensity of theactual situation, using the exhaust method, the various samplingpoints of the gas pumped into the trachea with focus on analysis ofair chamber and at the same time analysis of a sample point ofoxygen and SF6 gases.

For a 110KV change GIS rooms,the use of 6-channel detection of SF6 gas content and 6-channeldetection of oxygen content, respectively, to monitor the switch3.

System can be online displayedon the sampling point switch of the indoor SF6 and O2concentration, when the switch indoor concentration of SF6 and O2over the system alarm alarm threshold. (SF6 alarm threshold to1000ppm, the value can also be carried out in accordance withCouncil requirements change, LK303 warning system detection limitis 200ppm, concrete construction can be adjusted according to userrequirements. O2 alarm threshold is 19.6%.)

 

MainAdvantages:

¨       Detecting function of SF6 in ambient air, Alarm function when thevalue of SF6 is over the standard.

¨       Detecting function of O2 in ambient air, Alarm function when thevalue of O2 is under the standard.

¨       Forced ventilation function .while the value of SF6 is over 1000ppmor the value of O2 is under 19.6%,the ventilation fan will start toworking.

¨       Artificial setting alarm points

¨       Detecting function of temperature and humidity in ambientair

¨        Thetiming of ventilation function

¨       Artificial ventilation function

¨       Display function of last ventilation

¨       Real time display each kind of parameter

¨       Inquire function about historical data

¨        Infrared detection and Voice notification function

 

TechnicalSpecification

???Supply???    AC 85-265V??? 50/60Hz

???Power Consumption??? Main Unit ???25VA,  Sensor???5VA

???Alarm ContactCapacity???AC220V/7A   Normally open/ Normallyclose

???Blower ContactCapacity???AC220V/15A  Normally open

???Test precision ofsensor???    O2   ±1%FS

                        SF6    ???2%  measured Value

???Test range of sensor???      O2   (1.0~25.0)%

                        SF6      (1~1000)ppm

???Test Resolution of sensor???O2    0.1%

                        SF6      1ppm

???Communications???RS-485

???Temperature ???-55.0??? ~125.0???

???Humidity???10 ~ 99%RH

???Dimension???250mm×120mm×400mm

???Dielectric Strength??????2000V

???ElectromagneticCompatibility???Electrostatic DischargeGB/T14598.10-1998   step3

???Electrical Fast Transient???GB/T14598.14-1999   step3

???Lightning Strike???GB/T17626.5-1999   step3

 

 

 