The DACTS704D module start and stop the generator manually via push-buttons mounted on the panel or automatically depending upon a remote start input signal in AUTO mode.
DACTS704D monitors the engine, indicating the operational status and fault conditions, shutting down the engine automatically and giving a true first up fault condition of an engine failure by a COMMON ALARM LAMP. The LCD display indicates the fault. The user also has the facility to view the system operating parameters via the LCD display.
1. Main function
*automatically start and stop the generator.
*automatically shut down the diesel on fault condition.
*monitor 12 analogue as generator voltage, load current, generator speed, and so on.
*4 programable digital inputs and 4 programable relay outputs
*Remote communication RS232, free PC software for configuration.
*LCD display in English or Chinese, LED indicate
2. Specification
DC supply
Continuous voltage rating: 8 to 36V DC
Alternator inputs
AC input: 25 - 620V (L-L); 15 - 360V (L-N)
Relay outputs
Start & Fuel: 16A / 30V DC at supply voltage
Configurable 1-5: 5A / 30V DC at supply voltage
Configurable 6: 3A / 30V DC at supply voltage
Dimensions
Overall: 206mm(W)X 146mm(H)X 44mm(D)
Panel cut-out: 196mm(L)X 136mm(W).