Smart Pressure Transmitter
Range: 0~0.2 kPa to 0~35MPa
Output signal: 4~20mA DC
Power supply: 24V DC (10~30V DC)
Features of loading: Relation equation of loading impedance RL and power voltage
Vs: RL <= 50(Vs-12)
Indicator: Pointer-type linearity indication 0~100% scale mark or LCD indicator, LED indicator.
Explosion-proof: A. Explosion isolation d II BT4
B. Intrinsically safe ia II CT6
Positive and negative shifts: After positive and negative shifts of zero absolute values of upper-and-lower-limit values of span and measuring range not exceed 100% of upper limit of measuring range. ( smart type: Turn down ratio 20: 1, 40: 1, 100: 1)
Maximum positive shift is 500% of minimum adjusting span; Maximum negative shift is 600% of minimum adjusting span.
Temperature range: Amplifier operation temperature range: -29 ~ +93° C(LT type: -25 ~ +70° C);
The temperature range of silicone oil filled in measuring components: -40 ~ +104° C(LT type: -20 ~ +315° C)
Normal silicone oil: -40 ~ +149° C
Static pressure: 4, 10, 25, 32MPa
Humidity: Relative humidity 0~100%
Volume absorption: < 0.16cm3
Damping (phase step response): Silicone oil, generally between 0.2s and1.67s, continuous and adjustable.