HYR45S4-8-48 lightning protector with signal and power mainly use to all kind of date, Analog Signal Transmission network systems (computer, communication system). The features of product is low limit voltage and rapid response which can protect the network system from the damage of induction lighting strike and the voltage surge through the signal transmission line.
HYR45S4-8-48 Single part Power part
Working Voltage Un 8V DC-48V
Max. Working Voltage UC 110V DC-125V
Rated Working Current Io 100mA 2A
Rated Discharge Current (8/20μ ) In 3KA 3KA
Max. Discharge Current (8/20μ ) Imax 5KA 5KA
Protection Level Up(8/20μ ) ??20V ??60V
Response time tA ??10ns ??25ns
Transfer rate ??100MBit/s /
Insertion Loss aE <0.5dB /
Connector Type RJ45 (Female)
Standard Distribution line 1/23/6 45/78
Working Temperature -40º C~+70º C
Remarks: The Lightning Through-Flow is limited by the interface of RJ45.