Set range
A. Set value: Same as input range
B. Heat of side proportion band: Temperature input 1 to span or 0.1 to span * 0.1 to 100.0% of span voltage input
C. Refrigeration of side proportion band: Heat of side proportion1_1000%
D. Integral time: 1_3600sec * 2
E. Differential time: 1_3600sec * 3
F. Anti-reset windup (ARW): 1_100% * 4 of proportion band
G. Heat of side proportion cycle time: 1_100sec *5
H. Refrigeration of side proportion cycle time 1_100sec * 6
I. Dead band: Temperature input-10 -10 or -10.0 - +10.0 C [ F ] Voltage /current input span - 10.0 -+10.0% * 7
1. If proportion band setting for 0 C [ F], turn to ON - OFF action
2. If integral time setting for 0 sec, turn to PD action
3. If differential time setting for 0 sec, turn to PI action
4. If anti-reset windup setting for o%. D action turn to OFF
5. Current input needless setting cycle time
6. If dead band setting for negative, turn to superpose
Limit action
PID control ( 0N - OFF, P, PI, PD control )
A. Automatism perform function
1. Adjuster method: Limit period
2. AT period: 1.5
B. Automatism emendation, set changes, found of self-correction, Heating / cooling PID control action except