Metallurgy, Mineral & Energy
Water Flow Indicator
2016-11-04 05:03  Views:207
Price:Negotiable
Send Inquiry

I. ZSJZ water indicator is a component of automatic sprinkler system. The current in the pipe drives the lodicule and touches microswitch, then changes water signal into electric signal, connect with controller to starts up automatic fire alarm system, be used to examine operation of automatic sprinkler system and confirm fire area. It's suitable for wetdry preaction, circulation and foam spray system. 4 types: Flange, jointing, thread and saddle type.
The water indicator manufactured by us is beautiful appearance and compact structure, and install easy. Various specifications: DN50~200. Various connections: Flange, jointing, thread and saddle type. Saddle type especially is applicable to rebuilding and extension work, clamp-on pipework. It's convenient and quick to install.

II. Main parameters
1. Specification: DN50~200
2. Rated pressure: 0.14~1.6MPa
3. Sensitivity: 15~37.5L/min
4. Voltage: DC24V
5. Contact output: Normally open_NO; Normally close_NC

III. Figure of extemal form
The extemal form see F1F1F3 and F4. F1 is flange type, F2 is thread type, F3 is jointing type, F4 is saddle type.

IV. Install
1Make sure the flow direction of medium is the same with water indicator.
2Lamina shall not touch with inner pipe when install. Lamina and drive link can runs flexibly. Lamina should crimp to barrel when install and disassemble
3Debug: When the end of one area discharges water, indicator sends out alarm signal, if not, check the install direction of indicator and whether laminae locks or not, or adjust the nut.
4The plan of wiring

V. Maintenance

Trouble: Not work(No electric signal)
1. Failure cause: Inner pipe has rag, or the welding slag seize the lamina
Erase rag and welding slag
2. Failure cause: The install direction is incorrect.
Method: Adjust install direction
3. Failure cause: The attitude of nut for adjustment is incorrect.
Method: Open the end water tester and adjust the nut for adjustment

Trouble: Not restitute after work
Failure cause: The attitude of nut for adjustment is incorrect.
Method: Adjust the nut with counterclockwise

Trouble: Action unreliability
1. Failure cause: The specification of lamina is incorrect.
Method: Change the lamina
2. Failure cause: The attitude of nut for adjustment is incorrect.
Method: Adjust the nut