Model:-
# Name Type and Use Scope of Products
- - - -
Name | Type | Class | Use Scope |
Fire-resisting series | NH | A | A.D. rated voltage 8.7/15kv or less plastic insulating and fine-resisting power cable; A.D. rated voltage 450/750v or less plastic insulating and fine-resisting control cable and A.D. rated voltage 450/750v or less plastic insulating and fine-resisting cable |
B |
A |
B |
A |
B |
A |
B |
- - - -
# Technical Properties or Conditions
# Cable may undergo fire-proof test, reaching the requirement of GB/T18380.3;it may, under the flame temperature below 750-800,put1,000v voltage, and burn for 90 min, and the connecting fuse 3A will not break.
# Except for conductor, armor layer and certain material under special conditions, all material of cable are combustion-retardant, highly combustion-retardant, and fire-proof material.
# Finished cable conductor-resistance, insulation resistance, voltage test, current-carrying capacity, DC voltage test after laying and installing and partial discharge, etc, are all similar to various corresponding kinds of common cable kinds.
# Cable structure and size:
a.
Approx. overall diameter of fire-proof cable is about 1.5-3mm more than corresponding common cable according to different kinds.
b.
Reference weight of fire-proof cable is about 10-7% more than corresponding common cable according to different kinds.
c.
Conductor structure and others are equal to corresponding common cable.