Product Features:
1. Flexibility:
- Air Flow Range (1700-80,000 CFM), 0.79-37.8 m^3/s
- Full-Customized casing thickness 50 (standard)-90 mm. (Optional)
- Air Process: Cooling, Heating, Humidifying, Dehumidifying, Filtration
- Integration; Run around coil, Air-to-Air Heat Exchanger
- Vertical, Horizontal can be supplied
- Integrate Communication (BAS, or lon)
- Plug Fan (Open-Wheel fan) for Hygienic aspect
- Reduce Pressure door for Possitive pressure section
- Insulation can be supplied that PU PS, or Mineral wool
2. Eurovent Certified Performance:
- Air Flow at Total static pressure verified that technical data state.
- Cooling performance of unit compare with selection software
- Heating performance of unit compare with selection software
3. Casing Performance comply EN1886
- Casing Leakage test; (-) Class L1 (+) class L1 (L1 is the lowest air leakage from table).
- Filter Bypass Leakage: (-) Class F9 (+) Class F9 (Lowest Bapass leakage from table).
- Thermal Bridging Factor TB2 second from table.
- Casing Deflection D2 5/1000 m maximum deflection
4. Low Risk of condensation
- Thermal Break Panel (0.73 Thermal Bridging Factor) 50 mm. Panel
- 3D slope drain pan reduce water left on drain pan
5. High Cleanbility:
- Unit floor are the same level of door frame (no dust pocket in unit)
- No half close profile to make dust accumulation
- All section of unit are accessible
1