Model:AW-5
- Industrial chiller are widely used in plastics electronic manufacturing, electroplating, pharmacy, chemical engineering, ultrasonic cleaning cooling, and printing.
- imported America and Japan new compressors features builtin security protection, low noice, and low comsuption.
- Original Schneider electronic parts ensure stable and safe operation.
- Full stainless steel thick water- tank type evaporator and sheel and tube condensor features high efficiency of exchanging heat.
- Multi-function control panel with full operational steps,meet your simple, safe, convenient operation.
Technical parameters
Model Item | AW-05 | |
nominal cooling capacity | kcal/h | 12900 |
kw | 15 | |
input power | kw | 5.06 |
power supply | 3PH~380V 50HZ | |
refrigerant | type | R22 |
type of control | capillary | |
compressor | type | hermetic scroll |
power (kw) | 4.41 | |
condenser | type | shell and tube |
cooling water flow (m3/h) | 3.5 | |
inlet and outlet pipe diameter (inch) | 1-1/2 | |
evaporator | type | tank with coil |
chilled fluid flow(m3/h) | 2.58 | |
volume (L) | 60 | |
inlet and outlet pipe diameter (inch) | 1 | |
pump | power (kw) | 0.75 |
lift(m) | 20 | |
safety protection | compressor over temperature, over current, high and low pressure, phase sequence, phase-missing | |
weight | kg | 150 |
dimension | mm | 890*500*840 |
Note: 1.Nominal cooling capacity is according to:
Inlet chilled fluid temperature: 12°C
Outlet chilled fluid temperature: 7°C
Inlet cooling water temperature: 25°C
Outlet cooling water temperature: 30°C
2. Working Range:
The temperature range of chilled fluid is from 5°C to 35°C;
Temperature difference between inlet and outlet chilled fluid is from 3°C to 8°C.
The temperature range of cooling water is from 18°C to 35°C;
Temperature difference between inlet and outlet coooling water is from 3.5°C to 10°C.
We reserve the right to modify the above dimensions or parameters without further notice.