Cummins® YC160 diesel generating sets technical parameters
Genset model YC160
Shape dimension/ L x W x H mm: 2460× 930× 1630
Weight: 2040kg
Normal power: 200/160 kVA/kW
Standby power: 223/178kVA/kW
Rated voltage: 400/230V
Output frequency: 50Hz
Wiring way: Three-phase four-wire
Control system: Microcomputer control system
Vibration absorber system: High elastic rubber shock absorbers Engine
Engine model: 6CTAA8.3-G2
Type: Six -cylinder, inline
Intake way; Turbocharged inter-cooled
Oil type: API CD 15W-40
Fuel type: 0#diesel
Fuel consumption rate: 45.4L/h
Oil consumption rateFuel 0.5%L/h
Starting mode: DC 24V electric start
Speed regulation: Electricity adjustable
Exhaust temperature; 500C
The total capacity of cooling fluid: 28L
Conpression ratio: 16.5: 1
Cylinderbore/stroke: 114/135mm
Displacement: 8.3L
Fuel consumption: 45.4(L/h)
Noise 88dB(A)
Generator
Model(single bearing)
UCI274H1
Shape dimension/ L x W x H mm: 1110x668X774
Weight: 600kg
Power(normal/standby) kW
160/176
Excitation system
Brushless motivated
Protection grade
IP22
Winding pitch
2/3
The steady-state voltage adjustment rate
± 1%
Recovery time s
≤ 1.0
Wave form deviation factor THD
≤ 3%
Telephone harmonic factor THF
≤ 2%
Telephone disturbance factor TIF
≤ 50
Control system
Control module
UPWIN2210
Display content
Engine speed, the unit is in power, unit state (standby, start, stop, etc. ), clock, cooling water temperature, lubricating oil pressure, fuel oil level, battery voltage, unit three-phase voltages, unit three-phase phase voltage, frequency, line current, line current, active power, power factor, total runtime. The time, start times, input/output channel state, the unit operation in the malfunction of the popup menu directly shows fault information, etc.