It is used to transmit and distribute power on the power line of A. C. Rated voltage 0.6/1kV
Executive standard:
GB/T12706.1 (equal to the standard of IEC60502)
Working condition:
Long-term working temperature allowed by cable conductor shall be no more than 70 centigrade.
Max. Temperature of cable conductor shall be no more than 160 centigrade during short circuit(the longest lasting time shall be no more than 5 seconds).
Environment temperature for installation shall be no less than 0 centigrade.
Main technical parameter of cable:
Max. Value of conductor DC resistance shall meet the requirement of conductor of category 2 stipulated in GB/T3956 standard at 20 centigrade.
For single core cable without shielding, voltage test of 3.5kV under power frequency is put on for 5 minutes between conductor and water when be immersed in the water for one hour. For multi-core cable, between each insulated conductor and other conductor, voltage test of 3.5kV under power frequency is put on for 5 minutes without puncture of insulation.
Production Scope
See the table