Standard of Products
The product is manufactured according to the standards of GB 12527-90 (Aerial insulated cables of rated voltages up to and including 0.6/1kV) and IEC60502 (Extruded solid dielectric power cables for rated voltages from 1kV to 30 kV).
Operating Characteristics:
Uo/U 0.6/1kV;
Rated voltage Uo/U: 0.6/1kV
Max. Permissible continuous temperature for conductor:
PVC, PE insulated aerial cables: 70 degree;
XLPE insulated aerial cables: 90 degree;
Max. Short-circuit temperature of the conductor shall not execeed (5s maximum duration):
PVC insulated aerial cables: 160degree;
PE insulated aerial cables: 130degree;
XLPE insulated aerial cables: 250degree;
The installation ambient temperature should not below-20degree;
The bending radius of cables are recommend as follows:
When the Diameter of cables less than 25 mm: Not less than 4 times the Diameter of cables;
When the Diameter of cables not less than 25 mm: Not less than 6 times the Diameter of cables;
When the cables are used in alternating current system, rated voltage of cables should be at least equal the rated voltage of the system; When the cables are used in direct current system, rated voltage should not exceed than 1.5 times of the rated voltage of the cables.