Benefits:
. Obvious interference to other devices from power supply (such as interference, overvoltage). Interphase voltage is unbalanced >1.8% of rated voltage. Low impedance line (Power transformer is about 10 times of rated data of inverter).
. Large quantity of inverter mounted on the same power line but have to minimize line current.
. Power factor calibrating capacitor or power factor correcting unit applied.
Rated Voltage: φ 3/380V/50Hz or 660V/50Hz
Rated operating current: 3A to 2000A@40C Degree
Reactive Strength: Core- Winding 3000VAC/50Hz/10mA/10S Free of arcing breakage (tested in factory)
Insulation Resistance: 1000VDC, insulation resistance≥ 100MΩ
Reactor's noise is less than 65dB(to be measured at the point 1 meter away from the reactor horizontally)
Protection class: IP00
Insulation class: Above F
Standard: IEC289: 1987 Reactor
GB10229-88 Reactor (equivalent to IEC289: 1987)
JB9644-1999 Reactor for semi-conductor transmission