Vacuum Interrupter
Main Technical Specification
Type: TD24A-12/1250-25
Rated frequency 50/60Hz
Rated Voltage 12kV
Rated short-time power-frequency withstand voltage (1 min) 38kV
Rated lightning impulse withstand voltage 95kV
Rated Current 1250A
Rated short-circuit breaking Current 25kA
Breaking operations of rated short circuit breaking current 25 Times
Rated short-time withstand current 25kA
Rated duration of short-circuit 3s
Rated peak withstand current 63kA
Rated short-circuit making Current 63kA
Rated breaking current of single capacitor bank 400A
Rated breaking current of back-to-back capacitor bank 400A
Rated operating sequence O-0.3s-CO-180s-CO
Weight of movable parts 0.73kg
Storage life 20years
Mechanical endurance 10000Times
Contacts limit erosion 3mm
For more detailed information as well as the outline drawing, please leave me your email adress, I will contact you ASAP.